What Size Wire for a 40 Amp Breaker?
Short answer: a 40 amp breaker needs 8 AWG copper, in NM-B cable (8/2 or 8/3 with ground) or as THHN in conduit. With aluminum, use 8 AWG aluminum where 75°C terminations apply, or 6 AWG aluminum in cable limited to 60°C.
40 amp wire size by wiring method
| Wiring method | Copper | Aluminum |
|---|---|---|
| NM-B or UF cable (60°C) | 8 AWG | 6 AWG |
| THHN/THWN-2 in conduit, 75°C terminals | 8 AWG | 8 AWG |
Ground wire: 10 AWG copper or 8 AWG aluminum (Table 250.122 covers 40 A in the 60 A row).
8 AWG copper is rated exactly 40 A in the 60°C column, which is why it works with NM-B. It has headroom at 75°C (50 A). Aluminum is the reverse case: 8 AWG aluminum is 35 A at 60°C and 40 A at 75°C, so the wiring method changes the aluminum answer but not the copper one.
40 amp wire size by distance (240 V)
| Conductor | 50 ft | 100 ft | 150 ft | 200 ft |
|---|---|---|---|---|
| Copper | 8 AWG (1.0%) | 8 AWG (2.1%) | 6 AWG (2.0%) | 6 AWG (2.6%) |
| Aluminum | 8 AWG (1.7%) | 6 AWG (2.2%) | 4 AWG (2.0%) | 4 AWG (2.7%) |
Smallest conductor that meets both the 75°C ampacity for a 40 A circuit and a 3% voltage drop at 32 A (80% of the rating), 240 V single-phase, one-way distance. Percent drop in brackets. If the circuit uses NM-B cable or 60°C terminations, start from the 60°C column instead.
Maximum one-way run at 3% drop, 240 V
| Conductor | At 32 A (EV charger) | At 40 A (full rating) |
|---|---|---|
| 8 AWG copper | 144 ft | 115 ft |
| 6 AWG copper | 229 ft | 183 ft |
| 6 AWG aluminum | 139 ft | 111 ft |
| 4 AWG aluminum | 221 ft | 177 ft |
Worked example: 32 A EV charger in a detached garage
A hardwired Level 2 charger set to 32 A sits 120 feet from the house panel. Conductors are THHN/THWN-2 in PVC, and all terminations are rated 75°C.
- Circuit size: EV charging is continuous, so 32 × 1.25 = 40 A breaker and conductors.
- 8 AWG copper: 2 × 12.9 × 32 × 120 ÷ 16,510 = 6.00 V, or 2.5%. Acceptable.
- 8 AWG aluminum (40 A at 75°C): 2 × 21.2 × 32 × 120 ÷ 16,510 = 9.86 V, or 4.1%. Too much.
- 6 AWG aluminum: 2 × 21.2 × 32 × 120 ÷ 26,240 = 6.20 V, or 2.6%. Acceptable.
Result: 8 AWG copper with a 10 AWG copper equipment ground, or 6 AWG aluminum with an 8 AWG copper (or 6 AWG aluminum) ground. The aluminum hots were upsized from 8 to 6 AWG for voltage drop, so 250.122(B) grows the ground by the same circular-mil ratio: 10,380 × 26,240 ÷ 16,510 = 16,497 cmil, which 8 AWG copper (16,510) covers. Aluminum needs one size up for the same drop, which usually decides whether it saves money on a run like this. Try other distances in the voltage drop calculator.
Reproduce this example and save the calculation
Open the copper voltage-drop calculation, or compare 6 AWG aluminum. The result can be printed, saved as PDF or downloaded as text. These examples use actual load current for voltage drop; they do not size the breaker from 32 A alone.
Before ordering, record: the equipment nameplate and installation instructions; load duration; wiring method; termination rating; ambient temperature and conductor grouping; one-way run length; and the adopted code edition. Check the ground again if the circuit conductors increase for voltage drop. The table above assumes no additional temperature or grouping adjustment.
Common 40 amp circuits
- Cooktops and wall ovens. Many are rated for a 40 A circuit. Household ranges rated 8¾ kW or more need at least a 40 A branch circuit (210.19(C) in the 2023 NEC; 210.19(A)(3) in 2020). A double wall oven may need 50 A; check the installation manual.
- Level 2 EV charger at 32 A, as in the example above.
- Heat pumps and AC condensers. Use the nameplate MCA to size the wire and the MOCP for the breaker; a 40 A MOCP doesn't always mean 8 AWG is required if the MCA is lower.
- Tankless electric water heaters often use several 40 A circuits; follow the manufacturer's wiring diagram.
8/2 or 8/3? And what size conduit?
A cooktop or wall oven that uses only 240 V needs two hots and a ground (8/2 with ground). A range, or any appliance with 120 V controls, needs a neutral as well (8/3 with ground).
In conduit, two 8 AWG THHN plus a 10 AWG ground total 0.0943 in², which fits ½" EMT (40% of 0.304 in²). Add a neutral and the total is 0.1309 in², which needs ¾" EMT. Areas are from Chapter 9 Table 5; see the conduit fill chart.
Common mistakes inspectors flag
- 10 AWG on a 40 A breaker for a cooktop or oven. Only Article 440 equipment with a nameplate that allows it gets that exception.
- 8 AWG aluminum on a 40 A breaker where the 60°C column applies (60°C terminations, or SE cable run in thermal insulation per 338.10(B)(4)). It's rated 35 A there.
- Stranded 8 AWG forced into terminals listed only for smaller wire. Check the device's terminal range.
- A 50 A breaker on 8 AWG NM-B for a range. The cable is limited to 40 A.
Frequently asked questions
Can I use 10 gauge wire on a 40 amp breaker?
No, for a general circuit. 10 AWG copper is limited to 30 A by 240.4(D); see 30 amp wire size. The exception is equipment like AC condensers where the nameplate MCA and MOCP permit it under Article 440.
Is 8 gauge wire good for 40 amps?
Yes. 8 AWG copper is rated 40 A at 60°C and 50 A at 75°C. See the ampacity chart for other sizes.
What size wire for a 40 amp EV charger?
A charger that draws 40 A continuous needs a 50 A circuit, so 6 AWG copper NM-B or 8 AWG copper THHN at 75°C; see 50 amp wire size. A charger set to 32 A uses a 40 A circuit with 8 AWG copper.
How far can I run 8 gauge wire on a 40 amp circuit?
About 115 feet one way at a full 40 A on 240 V, or 144 feet at a 32 A load, before exceeding 3% drop. Past that, use 6 AWG copper. The wire size calculator handles other loads.
Last updated: November 6, 2026. Based on NEC 2023. Check results against the code edition and local amendments your jurisdiction enforces and with the AHJ; electrical work should be done by qualified people.
Sources
- NFPA 70, National Electrical Code, 2023 edition (NFPA offers free read-only access). Values on this page follow the NEC 2023; check the edition and local amendments your jurisdiction has adopted.
- Tables cited: Table 250.122 and Chapter 9, Table 5.
- Sections cited: 210.19(A)(3), 210.19(C), 240.4(D), 250.122(B) and 338.10(B)(4).
- How the numbers are checked: how we build our calculators.