Conduit fill calculator

10 conductors in 3/4" EMT: 25.0% fill. Within the 40% limit. Smallest passing trade size: 3/4" EMT.

Fill
25.0%
Allowed (Ch. 9 Table 1)
40%
Maximum conductors of this size
16
Conduit area (Table 4)
0.533 in²
Total conductor area (Table 5)
0.1330 in²
10 × 12 AWG THHN/THWN-2
10 × 0.0133 = 0.1330 in²
Method
Same size and insulation; Note 7 rounding where applicable.
Trade sizeInternal area (in²)FillResult
1/2" EMT0.30443.8%Over fill
3/4" EMT0.53325.0%Pass
1" EMT0.86415.4%Pass
1-1/4" EMT1.4968.9%Pass
1-1/2" EMT2.0366.5%Pass
2" EMT3.3564.0%Pass
2-1/2" EMT5.8582.3%Pass
3" EMT8.8461.5%Pass
3-1/2" EMT11.5451.2%Pass
4" EMT14.7530.9%Pass
Open shareable result

Calculation aid; verify against the adopted code and project conditions. Automated checks are not licensed professional review.